Place of use
These cables are used the places where are exposed high temperatures and low temperatures for lighting elements, tool and machines and furnaces, where are the environment temperatures are -60 C…+180 C.
Inner Conductor | Electrolytic Solid Annealed Copper Wire, IEC 60228, Class 1 |
Insulation | Slicon Compound EI2 |
Product Code | Dimension and Weights | Electrical Properties | |||||||||
Nominal Cross Section | Overall Diemeter ( ~ ) |
Net Weight ( ~ ) |
Standart Lenght | Max. Dc Conductor Resistance at 20◦ C | Current Carrying Capacity | ||||||
In Ground at 20° C | On Air at 30° C |
CONDUCTOR RESISTANCE | INSULATION RESISTANCE (MIN) | CURRENT CARRYING CAPACITY | OPERATING VOLTAGE | TEST VOLTAGE | BENDING RADIUS | TEMPERATURE RANGE | ||
mm² 0,75 1,0 1,5 2,5 4,0 6,0 10 16 25 35 50 70 95 120 150 185 240 | Ω/Km 24,5 18,1 12,1 7,41 4,61 3,08 1,83 1,15 0,727 0,524 0,387 0,268 0,193 0,153 0,124 0,0991 0,0754 | MΩxKm 20 | mm² 0,75 1,0 1,5 2,5 4,0 6,0 10 16 25 35 50 70 95 120 150 185 240 | A 13 16 20 25 34 44 61 82 108 135 168 207 250 344 420 490 580 | 300/500 V (H05S-K) 450/750 V (H07S-K&SİAF) | 2000 V | 10XD | -60ºC+180ºC |
FLAME RETARDANT TEST | SMOKE DENSITY TEST | CORROSIVE GAS TEST | HALOGEN-FREE TEST | FLAME PROPOGATION |
IEC 60332-1-2 VDE 0482-332-1-2 EN 60332-1-2 | IEC 61034-2 VDE 0482-1034-2 EN 61034-2 BS EN 61034-2 | IEC 60754-2 VDE 0482-267-2-3 EN 50267-2-3 BS EN 50267-2-3 | IEC 60754-1 VDE 0482-267-2-1 EN 50267-2-1 BS EN 50267-2-1 | IEC 60332-3-24 VDE 0482-332-3-24 EN 60332-2-24 |